JPC series

 

jpc 

Detail

Efficient, stable & maximize output power

High-power density modular design, supporting N + X parallel redundancy and cabinet in parallel, simple and fast to maintain, convenient and flexible to expand capacity

Advanced MPPT maximum power point tracking technology, compare with PWM pulse width modulation, increasing power generation up to 30%, it can save up to 30% solar panels

Intelligent fan speed control and a unique cooling concept design, effectively exhaust heat to ensure stable operation of controller unit

Advanced soft switching control technology, smaller switching loss, higher conversion efficiency

Wide input voltage range provides more flexible access solutions of solar panels, also according to requirements , you can choose buck mode module (high voltage, low current) or boost mode module (low voltage, high current) (see technical data)

Perfect protection design, safe and reliable

Hot-swap modules safety switch, no arc interrupter module operation quick disconnect technology provides security guarantees

Input and output over voltage, under voltage, module failure, reverse polarity, anti-polarity, over-temperature protection function protect equipment perfectly.

Intelligent battery management system

Choosing best charging mode according to the battery charging status, prolong battery life

Overcharge and over discharge protection functions send sound & light alarm timely, starting responsible protections automatically

Friendly human-machine interface, easy to use

Large touch screen LCD design, graphic visual display operating status at a glance

Data storage device alarm information stored for easy troubleshooting

Powerful monitoring function, easy management and maintenance

Remote monitoring and control system, unattended on station

Support software online upgrade

 

 

 Parameter

 

Model (L: Buck mode;

H: Boost mode)

JPC40L JPC60L JPC80L JPC100L JPC120L JPC140L JPC160L
JPC40H JPC60H JPC80H JPC100H JPC120H JPC140H JPC160H
Rated power (KW) 40 60 80 100 120 140 160
Output current (A) 100 150 200 250 300 350 400
Number of MPPT module 2 3 4 5 6 7 8
Input
Number of input string 2 3 4 5 6 7 8
Max power per string 20KW
Max current per string Buck mode: 50A; Boost mode: 80A
Max voltage per string Buck mode:  750Vdc; Boost mode: 430Vdc
Voltage range per string Buck mode: 350~700Vdc; Boost mode:150~400 Vdc
Output
Nominal output voltage 380Vdc
Voltage range 294~403 Vdc
Ripple 500 mVp-p
Efficiency Buck mode: 96.5%; Boost mode:96.0%
Accuracy of MPP tracking 99.9%
Accuracy of voltage ±1.0%
Dynamic response V:±5%Vo; recovery time: t: 500uS;
25%~50%~25% or 50%~75%~50% load, 0.1A/us; period 4ms 
System
Consumption 25W
Temperature coefficient ±0.02%/
Noise 60dB(A)
Cooling Force cooling
Degree of protection IP20
Communication RS485
Storage function Max 200 items at monitor module
Protection Buck mode: module failure, fan error, over temperature, over or low input voltage,
anti-polarity, over output voltage, short circuit, current flowing backwards, communication error, resistance input to ground, module loss, PV array error warning, input breaker warning;

Boost mode: module failure, fan error, over temperature, over or low input voltage,
over output voltage, short circuit, current flowing backwards, communication error, resistance input to ground, module loss, PV array error warning, input breaker warning;

Storage temperature -40~+70
Operation temperature -20~+55 (+55~+65 derating to 80%)
Environment temperature 0~95%, non-condensing
Altitude 0~4000m (decrease 1  per 200m above 2000m)
Dimension (W*D*H mm) 600x600x1500
Weight (Kg) 115 130 145 160 175 190 205